Description
BENTLY NEVADA 163179-02 — 3500/61 Six-Channel RTD/TC Temperature Monitor (with Recorder Outputs), Main Monitor Board

163179-02
Brand & Model Title
Bently Nevada (Baker Hughes) 163179-02 — 3500/61 Temperature Monitor, 6-Channel RTD/TC Machinery Protection Module with per-Channel 4–20 mA Recorder Outputs
The 163179-02 is the front monitor card of the 3500/61, the six-channel temperature monitor of the Bently Nevada 3500 machinery protection system. It is one half of a two-board module: the monitor card plugs into the front of the 3500 rack, and a matching rear I/O module (133819-02, 133827-02, 133835-02, 133843-02 or 136711-02) carries the field terminations. The 3500/61 is functionally identical to the 3500/60 (163179-01) except that it adds a 4–20 mA recorder output on each of its six channels — that, and nothing else, is what separates -01 from -02.
Main Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Machinery protection monitor module (front card), part of a two-board set |
| System | Bently Nevada 3500 Series; ordered as 3500/61-AA-BB (AA = I/O type, BB = approval) |
| Channels | 1–6, RTD or TC, mixed on the non-isolated I/O version |
| Thermocouple ranges | Type E −100…+1000 °C · J −18…+760 °C · K −18…+1370 °C · T −160…+400 °C |
| RTD ranges | Pt100 (α 0.00385) −200…+850 °C · Pt100 (α 0.00392) −200…+700 °C · Ni120 −80…+260 °C · Cu10 −100…+260 °C |
| Input impedance | 10 MΩ per lead |
| RTD excitation | 925 ±15 µA at 25 °C per transducer |
| Resolution | 1 °C or 1 °F |
| Accuracy | ±1 °C to ±3 °C at 25 °C depending on I/O module and rack type; cold-junction sensor ±1 °C at 25 °C |
| Recorder outputs | +4…+20 mA per channel, proportional to full scale; 0…+12 Vdc compliance; 0…600 Ω load |
| Recorder resolution | 0.3662 µA/bit; ±0.15 % at room temperature, ±0.4 % over the operating range |
| Alarms | Alert and Danger, over and under, 0–100 % of full scale; setpoint accuracy within 0.13 % of desired value |
| Alarm delays | Alert 1–60 s in 1 s steps; Danger 1–60 s in 0.5 s steps |
| Isolation | TC-isolated I/O: 500 Vdc system, 250 Vdc channel-to-channel |
| Redundancy | TMR operation when three monitors are installed adjacent to each other |
| Power consumption | 9 W nominal (3500/60 is 7 W) |
| Rack space | 1 full-height front slot + 1 full-height rear slot |
| Monitor dimensions / weight | 241.3 × 24.4 × 241.8 mm / 0.91 kg |
| I/O module dimensions / weight | 241.3 × 24.4 × 99.1 mm / 0.45 kg (internal-barrier version 163.1 mm deep, 0.46 kg) |
| Operating / storage temperature | −30…+65 °C (0…+65 °C with internal-barrier I/O) / −40…+85 °C |
| Compliance | API 670; SIL 2 capable at system level; FCC Part 15, EMC 2014/30/EU, LVD 2014/35/EU, RoHS, DNV GL, ABS |
| Hazardous area | CSA/NRTL/C Class I Div 2 and Zone 2; ATEX/IECEx II 3 G (II 3(1) G with internal barriers), T4 at −20…+65 °C |
Typical Applications
- Bearing metal temperature on steam and gas turbines, compressors, gearboxes, large pumps, motors and generators — the classic API 670 protection loop
- Generator and motor stator winding temperature monitoring, where the 4–20 mA recorder output is fed to the DCS or historian for trending alongside the trip logic
- Compressor suction/discharge and lube-oil/seal temperatures in oil & gas, LNG and petrochemical service
- Turbine exhaust and process temperature monitoring in combined-cycle and industrial power plants
- Rebuilds and module expansion of existing 3500 racks — the 3500/61 is the standard upgrade when an existing 3500/60 installation needs an analogue trace without adding a separate transmitter
- TMR protection chains on critical machines, where three 3500/61 monitors are grouped in adjacent slots and voted
Related News & Events
- “-01 vs -02” is a model number, not a revision. At least one reseller states that “163179-02 is a revised-firmware functionally equivalent replacement for 163179-01”. That is wrong and expensive: -01 is the 3500/60 (no recorder outputs) and -02 is the 3500/61 (with recorders). Fitting a -01 where a -02 was ordered silently removes the 4–20 mA signals your historian depends on, with no alarm to tell you.
- The most common ordering error is an unmatched rear I/O module. A -01 (non-isolated, internal termination) rear card does not behave like a -03 (TC isolated); plants that mix them end up chasing ground loops for days. Always confirm the rear module part number and the AA code together with the monitor.
- The card carries no configuration. Sensor type, range, alarm setpoints, recorder scaling and TMR voting all live in the rack configuration, not on the board. Replacing a monitor without restoring the exported configuration will leave trips disabled or produce nuisance trips — and in a TMR group, all three monitors must match in configuration and sensor assignment or voting integrity is lost.
- SIL 2 is a system claim, not a board claim. The 3500 platform can be used up to SIL 2 when the whole loop — sensors, barriers, modules, output path — is configured and certified as such. A -02 board alone does not make a loop SIL 2.
- Counterfeits are a real risk on this part number. The 3500 range is one of the most cloned product lines in the secondary market. Check label printing quality, connector mouldings, PCB finish and serial-number consistency, and buy from a channel that will let you bench-test in a known-good rack (OK / TX-RX / Bypass LEDs, channel continuity, recorder output against a simulated RTD).
- Unlike the Moore APACS hardware in this series, the 3500 platform is still current. Baker Hughes continues to build and support the 3500 system, so genuine new modules, factory repair and firmware support remain available — the trade in used 163179-02 units is driven by price and lead time, not by obsolescence.
- Recorder-loop sanity check: the output is +4…+20 mA into a maximum 600 Ω load with 12 V compliance. Adding a 250 Ω sense resistor plus a long cable run plus a DCS input can exceed that budget; check the loop before blaming the module.