Description
150-B97NBDB — Allen-Bradley (Rockwell Automation) SMC Dialog Plus Smart Motor Controller, 97 A, Open Type
Brand & Model Title
Allen-Bradley 150-B97NBDB — SMC Dialog Plus™ Smart Motor Controller (Bulletin 150), 97 A Continuous, 200–480 V AC 3-Phase, Open-Type (Panel Mount), Soft-Start Solid-State Motor Controller
The 150-B97NBDB is a solid-state smart motor controller of the Allen-Bradley SMC Dialog Plus family (the “B” execution of Bulletin 150). Using microprocessor-controlled thyristor voltage ramping, it provides smooth acceleration/deceleration for three-phase motors — 75 HP @ 460 V (30 HP @ 230 V) — with multiple start/stop modes, integrated electronic motor protection, onboard metering, and a local LCD/keypad interface, plus SCANport communication for Rockwell automation integration.

150-B97NBDB
Main Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Solid-state smart motor controller (soft starter), SMC Dialog Plus |
| Manufacturer | Allen-Bradley / Rockwell Automation (USA origin) |
| Rated current | 97 A continuous (maximum recommended fuse: 350 A per family ratings) |
| Line voltage | 200–480 V AC, 3-phase, 50/60 Hz (rated operating voltage marked 480 V AC) |
| Motor capacity | 75 HP @ 460 V AC; 30 HP @ 230 V AC (≈55 kW @ 400 V) |
| Control supply | 100–240 V AC, 50/60 Hz, single-phase (10 A max @ 250 V circuit) |
| Starting modes | Soft Start, Soft Start with Kickstart, Current Limit, Dual Ramp, Full Voltage |
| Stopping modes | Soft Stop, Pump Control, Accu-Stop, Smart Motor Braking (SMB) |
| Slow-speed jogging | 7% / 15% of base speed (selectable) |
| Ramp ranges | Start 2–30 s; Stop 2–120 s; stall delay 0–10 s; jam-detection delay 0–10 s |
| Protections | Electronic overload, stall, jam, phase loss, voltage unbalance, over-temperature, excessive starts-per-hour |
| Metering | 3-phase current, line voltage, power factor, kW, kWh, elapsed time, motor thermal load |
| Human interface | Onboard LCD digital display + 4-key keypad; parameter download via DriveTools |
| Communication | SCANport (standard onboard); DeviceNet/ControlNet/EtherNet-IP via optional plug-in modules |
| Enclosure | Open type (panel/cabinet mount, IP20/NEMA 1 category) |
| Environment | Operation 0…+40…50 °C (derating above 40 °C per datasheet; listings cite 0–50 °C); storage −20…+70 °C; 5–95% RH non-condensing |
| Heat dissipation | Peak ~285 W (thyristor losses at full load) |
| Wiring | Max 50 mm² / 1 AWG per power terminal; 12 N·m terminal torque |
| Dimensions / weight | ~305 × 248 × 256 mm (12 × 9.77 × 10.09 in); ~11.1–11.3 kg |
| Certifications | UL 508 Listed, CSA Certified, CE; family compliance with EN/IEC 60947-1 |
Typical Applications
- Pumps and fans — soft start/soft stop and pump-control curves to eliminate water hammer and pressure surges in water/wastewater and HVAC systems
- Conveyors and material handling — controlled acceleration avoiding belt slippage and product spillage
- Compressors, mixers, crushers — current-limit start reducing inrush from 5–7× FLA (DOL) to controlled limits, easing generator/grid stress
- Chiller and HVAC retrofits — integrated start/stop control in standard MCC configurations
- Legacy MCC maintenance — replacement spare for the large installed base of SMC Dialog Plus units in plants standardized on Rockwell motor control
Related News & Events
- Product family status — discontinued: the SMC Dialog Plus (Bulletin 150 “B” series) is out of production; Rockwell’s current soft-start portfolio is the SMC Flex (150-C) and SMC-50 (150-E) families, which carry forward the same start/stop modes plus EtherNet-IP and updated protection. The 150-B97NBDB is supplied today as new-surplus, refurbished, or repaired units through industrial resellers (DO Supply, Radwell and similar, typically 1–2 year dealer warranties) — factory warranty no longer applies.
- Series/firmware lineage: field units span series revisions A through F with firmware families V1.x through V5.x+; parameter sets differ across firmware generations, so buyers should match series/firmware or be prepared to re-parameterize after replacement.
- Bypass confusion in the market: several reseller pages claim “integrated bypass contactors.” The open-type SMC Dialog Plus 97 A unit is a thyristor controller; internal bypass is not a standard feature of the base 150-B97NBDB — external bypass contactors are commonly added in the panel to cut full-speed heat loss (~285 W peak dissipation). Verify against the official 150-B datasheet before assuming bypass operation.
- Market caution — conflicting claims: third-party listings vary widely (200–600 V range, 500 HP, “Size 5 NEMA contactor,” “built-in DeviceNet,” origin “Republic of Korea,” 0–40 °C vs 0–50 °C operation). The consistent official picture: 97 A, 200–480 V AC, 75 HP @ 460 V, open type, control 100–240 V AC — treat divergent figures as fabricated until checked against Rockwell publication 150-B.