Description
140DDO84300 is a 16-point DC discrete output module for the Modicon Quantum 140 series automation platform (Schneider Electric). It converts PLC logic commands into field output signals, driving loads such as relay coils, solenoid valves, indicator lights, and small contactors from a Quantum I/O rack.

140DDO84300
Key Features
- 16 DC outputs organized in 2 isolated groups of 8 channels
- Wide voltage range: 10–60 V DC output (absolute max 72 V), compatible with 24 V / 48 V / 60 V field devices
- Sink (negative logic) output type — load common is +V, module switches the return side
- High current capacity: 2 A per point, 6 A per group, 12 A per module
- Fast response: ≤1 ms (both ON and OFF transitions)
- Built-in protection: internal fuses — 2 A per point, 8 A per group
- Strong isolation: 2500 Vrms DC channel-to-bus, 700 Vrms DC group-to-group
- Diagnostics: 16 green channel status LEDs, 1 red external-fault LED, 1 green bus-communication LED; hot-swappable replacement
Technical Specifications (typical)
| Parameter | Value |
|---|---|
| Model | 140DDO84300 |
| Platform | Modicon Quantum |
| Output channels | 16 (2 groups × 8) |
| Output voltage | 10–60 V DC |
| Load current | 2 A/point, 6 A/group, 12 A/module |
| Voltage drop | ≤1 V at 2 A |
| Leakage current | ≤1 mA at 60 V |
| Response time | ≤1 ms |
| Bus current draw | 160 mA |
| Power dissipation | 1 W + (1 V × total module load current) |
| Operating temperature | 0–60 °C (storage −40 to 85 °C) |
| Weight | 0.45 kg |
| Addressing | 1 output word |
Certifications
CE, UL 508, CSA C22.2 No. 142, FM Class 1 Division 2, C-Tick, GOST, RMRS.
Typical Applications
Power generation, petrochemical, water/wastewater treatment, and discrete manufacturing — used for sequence control, interlock protection, and status indication within Quantum PLC systems.
Wiring/Selection Notes
- Output logic is sink type — verify it matches your field wiring scheme before procurement.
- Keep Group 1 and Group 2 supply returns separate; total load must stay within 6 A/group and 12 A/module limits.
- If a red fault LED appears, check for shorted loads, reversed polarity, or exceeded group current.