Product Overview

CC-PAOH01 belongs to Honeywell Experion PKS Series C I/O family, it is a 16-channel analog output IOM with native HART protocol support, working with C300 controller via IOLINK bus. It converts digital control signals from C300 into 4–20mA analog output to control field control valves, positioners and HART smart actuators. It supports HART bi-directional communication to read valve diagnostic information, device tag, calibration data from field HART instruments. This module needs to pair with IOTA terminal assembly for field wiring. It is widely used in petrochemical, refining, power plant DCS control loops. CC-PAOH01 is legacy Series C IOM; CC-PAOH51 is its updated revision.

Honeywell CC-PAOH01

Key Technical Specifications

  • Part Number: CC-PAOH01, 51405039-175
  • Manufacturer: Honeywell
  • Series: Experion PKS Series C I/O, AO-HART
  • Channels: 16 isolated analog output channels
  • Output signal: 4–20mA, HART 5/7 protocol
  • Resolution: 0.05% FS
  • Accuracy: ±0.35% FS @25°C
  • Max load resistance: 800Ω (24V field supply)
  • Response time: Settles within 1% of final value ≤80ms
  • Fail-safe mode: Per-channel configurable, Hold last value / low / high safe value
  • Diagnostics: Open-circuit detection, overcurrent, module health, HART device status
  • IOTA terminal assembly:
    • Non-redundant: CC-TAOX01 (6 inch)
    • Redundant: CC-TAOX11 (12 inch)
  • Communication: IOLINK to C300 controller
  • Power: Powered by Series C I/O rack backplane
  • Operating Temp: 0 ~ +60°C
  • Storage Temp: -40 ~ +85°C
  • Humidity: 5–95% non-condensing
  • Certification: CE, UL, Class I Div 2 hazardous area approval
  • Weight: ~0.48kg

 

Recommended 8 Similar Series C I/O Models

  1. CC-PAOH51 (Updated HART AO replacement for CC-PAOH01)
  2. CC-PAOX01 (16CH analog output without HART)
  3. CC-PAIH01 (16CH HART analog input)
  4. CC-PAIX01 (16CH analog input non-HART)
  5. CC-PDIS01 Digital Input Series C
  6. CC-PDOX01 Digital Output
  7. CC-TAOX01 IOTA terminal block (match CC-PAOH01)
  8. CC-CF01 C300 controller

 

Quality Control & Test Standard Operating Procedure (SOP)

  1. Visual Inspection: Inspect PCB, edge gold fingers, front panel LEDs, connector and label, confirm PN CC- / 51405039-175, check burnt marks, corrosion, bent pins.
  2. Continuity Test: Check backplane edge connector pins, power and signal lines for open/short circuit.
  3. Insulation Resistance Test: Insulation test between backplane power and each AO output channel.
  4. Power-Up Functional Test: Install on Series C rack with IOTA, apply rack power, verify LED boot sequence, no overheating.
  5. DAC Output Calibration Test: Send digital setpoints, measure each channel 4–20mA output, verify linearity & accuracy.
  6. HART Communication Test: Connect HART field device simulator, verify HART polling, tag read, diagnostic data exchange.
  7. Fail-safe & open-circuit test: Simulate field wire break, verify open circuit alarm; trigger communication loss, check fail-safe action.
  8. IOLINK Bus Communication Test: Connect with C300 controller, verify control setpoint download and diagnostic upload.
  9. Environmental Burn-in Test: Powered burn-in under rated temperature for early failure screening.
  10. Final Recheck & Documentation: Repeat mA output and HART test, generate serial-number traceable test report before anti-static packaging.

 

New Module Installation Guide

  1. Pre-Install Preparation: Execute LOTO lockout-tagout for DCS cabinet. Wear ESD wrist strap. Confirm CC- compatible with firmware and matched IOTA (CC-TAOX01 / CC-TAOX11).
  2. Rack & IOTA Inspection: Inspect Series C rack backplane and IOTA terminal block connectors, check oxidation or damage.
  3. Module Insertion: Plug CC- into IOTA base assembly, lock module latch.
  4. Field Wiring: Wire 4–20mA / HART field cables on IOTA terminals, use shielded twisted pair, follow Honeywell grounding rules.
  5. Power Restore: Energize rack 24VDC power, observe module LED initialization and IOLINK link status.
  6. Commissioning: Launch Experion PKS engineering station, import module configuration, assign channel tags, set fail-safe parameters, activate HART device polling.
  7. Loop Test: Send setpoints to each channel, measure 4–20mA output, read HART instrument information, verify alarm & diagnostic function.
  8. Post-Installation Documentation: Record serial number, channel configuration, HART device list and commissioning report into plant asset log.

 

Application Scenarios & Features

Application Scenarios

  • Honeywell Experion PKS DCS for petrochemical, refinery, natural gas process control
  • Thermal power plant boiler control, regulating valve control loops
  • HART smart valve positioner control and remote device diagnostics
  • Spare replacement for failed Series C AO-HART IOM in existing systems

Core Features

  • 16-channel 4–20mA analog output with built-in HART communication
  • Bi-directional HART communication to read smart valve diagnostics, tag and calibration info
  • Per-channel open-circuit detection and configurable fail-safe state for process protection
  • High precision DAC with good linearity for continuous regulating control
  • Works together with IOTA terminal assembly, supports redundant IOTA option
  • Plug-in hot-swappable Series C IOM for Experion PKS controller
  • Suitable for non-incendive hazardous area Class I Div 2

Honeywell CC-PAOH01

FAQ

Q1: What is difference CC- vs CC-PAOH51?

A1: CC- is older original version; CC-PAOH51 is upgraded revised model, drop-in replacement with improved component reliability, same IOTA compatible.

Q2: What is IOTA?

A2: IOTA (Input Output Termination Assembly) is the base wiring terminal assembly. The IOM module (CC-) plugs onto IOTA, field cables land on IOTA terminals.

Q3: Can CC- hot swap?

A3: Mechanically hot plug supported. If channels are controlling live regulating valves, removing the module will lose valve control; replace only in maintenance shutdown window.

Q4: Is CC- SIL certified?

A4: This is basic process control I/O module, not SIL safety rated. SIL safety application needs Honeywell Safety Manager SIS hardware.

Q5: What common failures of CC-?

A5: DAC drift, output channel driver damage, gold finger oxidation, HART modem circuit failure, terminal block wiring corrosion.

Q6: Is CC- discontinued?

A6: Legacy Series C IOM, Honeywell stopped new production; only surplus new or refurbished spare stock available for existing Experion PKS plants.

Q7: Difference between CC- and CC-PAOX01?

A7: CC-: AO with HART. CC-PAOX01: AO without HART, only 4-20mA analog output, no HART communication.

Q8: What controller does CC- pair with?

A8: Honeywell controller over IOLINK bus under Experion PKS DCS.