1606-XL240DRT — Allen-Bradley (Rockwell Automation) Bulletin 1606-XL Redundant DIN-Rail Power Supply, 24 V DC / 240 W

Related Product Recommendations

Model Description
1606-XLE240ERZ Current-generation redundant 240 W supply (24 V/10 A, 39 mm, plug-in, hot-swappable) — official successor
1606-XLE240E series (EE/EL/EDRZ)​ Essential-line 240 W single supplies, 120% power boost, DC-OK relay
1606-XLS240E… Performance-line 240 W supply with 150% power boost
1606-XL480DR / XL480DRT 480 W redundant sibling of the same XL generation
1492-SPU1C100 Recommended supplementary circuit protector for the primary side
1606-XLEP240 / buffer modules (1606-XLBF…)​ Buffer modules to extend hold-up time for safe shutdown
1606-XLE / XLS 480 W & 960 W frames Upgrade path for larger control-power budgets
Bulletin 1609 UPS Industrial UPS line where AC ride-through beyond the hold-up window is required
Category: Brand:

Description

1606-XL240DRT — Allen-Bradley (Rockwell Automation) Bulletin 1606-XL Redundant DIN-Rail Power Supply, 24 V DC / 240 W

 

Brand & Model Title

Allen-Bradley 1606-XL240DRT — Bulletin 1606-XL Switched-Mode Power Supply, 24 V DC / 10 A / 240 W, N+1 Redundant-Capable, DIN-Rail Mount (Redundant “DR/T” Execution)​

The 1606-XL240DRT belongs to Rockwell Automation’s Bulletin 1606-XL switched-mode power-supply family — the predecessor generation of today’s 1606-XLE/XLS/XLP/XLB lines. It delivers stabilized 24 V DC control power for PLCs, I/O, drives and field instrumentation, and is distinguished by its N+1 redundancy capability with RDY relay contact and DC-OK signaling: units can be operated in parallel on a decoupling basis so that a single-supply failure never drops the control bus. The official Rockwell application note (1606-AP035) for the 1606-XL240DR family documents the platform’s electrical behavior; the “-T” execution is the later hardware revision of the same redundant 240 W design.

1606-XL240DRT

Main Technical Specifications (per official 1606-AP035 / XL-family documentation)

Parameter Value
Product type Redundant-capable switched-mode DIN-rail power supply
Family Bulletin 1606-XL (predecessor of the current 1606-XLE/XLS families)
Output 24 V DC, 10 A rated, 240 W; soft output characteristic for balanced parallel current sharing (25.2 V ±2% no-load → 24 V ±0.5% at nominal load)
Power reserve 20% boost — 12 A short-term at ≤45 °C; overload up to ~1.6 × INom with gradual voltage reduction (no shutdown, no hiccup)
Input (AC) 100–120 / 200–240 V AC switchable, 47–63 Hz (accepts 85–132 / 176–264 V AC)
Input (DC) 240–375 V DC (mode switch left in 230 V position); 8 mA at open output — battery-source friendly
Input current < 6 A (115 V position), < 2.8 A (230 V position); inrush < 30 A at 264 V AC cold start
Primary protection 10 A slow-blow (HBC) fuse or 1492-SPU1C100 supplementary protector recommended
Transient immunity VDE 0160 / W2 (750 V / 1.3 ms), all load conditions
Hold-up time > 25 ms at 196 V AC, 24 V / 10 A
Efficiency / losses ~89% typical; ~26.7 W losses at 230 V AC full load
MTBF 390,000 h (Siemens Norm SN 29500, 40 °C); 105 °C long-life electrolytic capacitors
Signaling DC-OK LED front indicator; RDY relay contact for redundancy/DC-OK supervision
Environment Operation 0…+70 °C (derating above 60 °C); storage −25…+85 °C
Mounting Standard 35 mm DIN rail; convection-cooled, fanless
EMC Radiated EMI below EN 50081-1 even with long unscreened output cables
Certifications UL Listed (C-UL-US), CE
Output protection Short-circuit, open-circuit and overload protected; high short-circuit current provides a large “start-up window” for awkward loads (DC-DC converters, motors)

 

Typical Applications

  • N+1 redundant 24 V control buses — two or more units paralleled so a single-supply failure never interrupts PLC/DCS control power; RDY contact wired to the controller for automatic supervision
  • PLC / ControlLogix cabinet power — stabilized 24 V DC for processors, I/O, networks and HMIs
  • Inductive and capacitive awkward loads — the high short-circuit current design starts DC-DC converters and contactor/motor loads reliably without fold-back “sticking”
  • Process-industry control panels — wide AC/DC input tolerance handles unstable grids and 240–375 V DC battery-backed feeds
  • Legacy fleet maintenance — replacement/upgrade spare for the large installed base of 1606-XL supplies in Rockwell-standardized plants

 

Related News & Events

  • XL family retired from the catalog:​ Rockwell’s current switched-mode portfolio is organized as 1606-XLS (Performance), 1606-XLE (Essential), 1606-XLP (Compact) and 1606-XLB (Basic); the plain 1606-XL generation — including 1606-XL240DRT/DR — has been phased out of the active catalog and official product pages, so documentation now survives mainly in the literature library and archived application notes (e.g., 1606-AP035). Supply today is through new-surplus and tested-stock channels with dealer warranties.
  • Official successor path:​ Rockwell positions the 1606-XLE240ERZ redundant power supply (24 V, 10 A, 240 W, 39 mm width, plug-in terminals, DC-OK relay, hot-swappable, ~94.7% efficiency, Active lifecycle) as the modern equivalent, with the 1606-XLE240E series serving single-supply duty in the same power class.
  • Naming discipline:​ distributor pages for this reference are heavily AI-contaminated — claims of “30 W / 1.3 A”, “720 W / 30 A”, “PROFIBUS interface”, “−40…+70 °C”, “MTBF 1,000,000 h” and random dimensions/weights all circulate. The authoritative platform is the 24 V / 10 A / 240 W N+1-redundant supply per the official 1606-AP035 note; always confirm the nameplate before ordering.
  • Engineering notes in circulation:​ at DC input the 115/230 V selector must remain in the 230 V position; parallel balancing relies on the soft output characteristic — do not mix XL240DRT units with different-family supplies on one redundant bus without decoupling diodes/mosfets; verify the RDY contact wiring after any swap since it is the only automated failure signal.