Triconex 3005 TMR Main Processor Module for Tricon SIS
Executive Summary
The Triconex 3005 is a triple modular redundant main processor module for the classic Tricon Safety Instrumented System (SIS). Three 3005 modules must be installed in the main chassis to build a complete 2-out-of-3 (2oo3) fault-tolerant controller. It executes user safety logic, collects and votes I/O data via TriBus high-speed synchronization bus, supports SOE sequence-of-event recording, and handles communications with I/O racks and gateway modules. Comprehensive onboard self-diagnostics continuously monitor processor, memory and bus health. It supports hot-swap maintenance and meets IEC61508 SIL3 functional safety requirements. Widely deployed in oil & gas, petrochemical, power and chemical ESD emergency shutdown and fire & gas protection systems, it is a critical spare CPU card for legacy Tricon cabinet overhaul and maintenance.
Core Technical Specifications
- Manufacturer: Triconex (Schneider Electric / Invensys, USA)
- Model: 3005
- Product Type: TMR Main Processor (MP) Module
- CPU: Motorola MPC860, 32-bit, 50MHz
- Memory: 16MB DRAM; 32KB battery-backed SRAM; 6MB Flash PROM
- Redundancy Architecture: Triple Modular Redundancy (TMR), 2oo3 hardware voting
- Inter-processor Bus: TriBus @25Mbps with 32-bit CRC data integrity check
- Supported Firmware Version: Tricon V9.2 and above
- Safety Certification: IEC61508 SIL3
- Power Supply: Powered by Tricon rack backplane dual redundant power rails
- Operating Temperature: 0℃ ~ +60℃
- Storage Temperature: -40℃ ~ +85℃
- Relative Humidity: 5% ~95%, non-condensing
- Status LEDs: PASS, FAULT, RUN/ACT indicators
- Mounting: Slide-in card for Tricon main chassis slot (3 units required for full TMR rack)
- Net Weight: Approx. 2.0 kg
- Origin: United States
Main Features & Advantages
- TMR triple redundant computing: Three processors run identical safety logic independently. Single point hardware fault cannot interrupt safety control execution.
- High-precision SOE time-stamping: Captures and time-stamps alarm and trip events, supporting root-cause analysis after plant shutdown.
- TriBus synchronization bus: 25Mbps proprietary inter-processor bus with CRC verification to guarantee reliable voting data exchange.
- Full-range online self-diagnosis: Real-time detection of CPU, memory, bus and internal hardware faults; fault information reported via front LED and TriStation engineering software.
- Hot swap capability: Individual processor module can be replaced online while SIS remains running to reduce plant downtime.
- Flash firmware storage: Firmware can be upgraded without chip replacement via engineering workstation connection.
- SIL3 functional safety compliance: Designed for safety-critical ESD, F&G and burner management interlock loops.
- Native compatibility with full Tricon I/O series: Works seamlessly with Tricon analog/digital I/O, communication and FTA termination assemblies.
Application Scenarios
- Petrochemical refinery ESD emergency shutdown control system
- Offshore platforms and natural gas pipeline fire & gas safety protection
- Thermal power plant boiler and turbine safety interlock protection
- Hazardous chemical process safety instrumented shutdown system
- Tank farm high-risk area safety protection controller core
- Legacy Tricon TMR main rack CPU replacement and system retrofit
- Fertilizer and fine chemical plant safety interlock control
Recommended Related Models (8pcs)
- 3006 Earlier generation Tricon Main Processor Module
- 3008 Upgraded Tricon Main Processor Module
- 3625 16-channel TMR Digital Output Module
- 3503E TMR Digital Input Module
- 3721 32-channel Analog Input Module
- 4351B TCM Communication Module
- 8111 Tricon Chassis Redundant Power Supply
- 9563-810 Digital Input FTA
FAQ
Q1: What is Triconex 3005? A: Triconex 3005 is Tricon TMR main processor module. Three modules are required together to form the core of SIL3 safety controller, executing safety logic and performing 2oo3 hardware voting.
Q2: What is the difference between 3005, 3006 and 3008? A: 3005 is the older MP version for Tricon V9.2+; 3006 is enhanced version; 3008 supports newer firmware V9.6 and above, with optimized memory and Ethernet firmware upgrade function.
Q3: Is Triconex 3005 still in production? A: Classic Tricon series including 3005 has been discontinued by Schneider Triconex. Available stock includes original new surplus and fully tested refurbished modules.
Q4: Must three 3005 modules be installed together? A: Yes. The Tricon main chassis needs three 3005 processors to realize the 2-out-of-3 TMR fault tolerant voting mechanism.
Q5: Does 3005 support hot swap? A: Yes, single 3005 processor supports hot swap. Site maintenance must follow LOTO lockout-tagout and safety work permit procedures.
Q6: What is TriBus? A: TriBus is Triconex proprietary high-speed bus for three processors to synchronize scan data and complete majority voting.
Q7: What is SOE function? A: Sequence of Events, which records high precision time stamp of field signal changes for post-trip event sequence analysis.
Q8: What are common faults of 3005? A: Backup battery depletion for SRAM, flash firmware corruption, TriBus communication error, memory failure and PASS/FAULT diagnostic alarm.