Description
SIEMENS MOORE 16137-222 — APACS+ / QUADLOG M-Bus “A” Side Cable, 2.5 Meter, Short-Span Module Bus Interconnect

16137-222
Brand & Model Title
Siemens Moore (Moore Products Co. heritage) 16137-222 — APACS+ / QUADLOG Cable, M-Bus “A” Side, 2.5 m, Shielded Pre-Terminated Module Bus Cable Assembly (Primary Channel, Short Cabinet Span)
The 16137-222 is a cable assembly, not a module. The OEM spare-part catalogue entry reads exactly “APACS+/QUADLOG CABLE, M-BUS A, 2.5M” — the 2.5-metre primary (“A”) channel of the Moore APACS+ / QUADLOG Module Bus, and the short-span alternative to the 4 m 16137-151. It belongs to a coherent four-part 2.5 m block, which is the cleanest way to remember this part of the catalogue: 16137-222 = M-Bus A, 16137-223 = M-Bus B, 16137-224 = I/O Bus A, 16137-225 = I/O Bus B — all 2.5 m. Ordering the wrong member of that block is the single most common mistake with this reference.
Main Technical Specifications
| Parameter | Value |
|---|---|
| Product type | Pre-terminated shielded bus cable assembly (passive interconnect) |
| Function | M-Bus (Module Bus) “A” side — primary channel |
| Platform | Moore APACS+ and QUADLOG DCS |
| Length | 2.5 m (8.2 ft) |
| Redundant partner | 16137-223 — M-Bus “B” side, 2.5 m |
| Related 2.5 m block | 16137-224 (I/O Bus A) · 16137-225 (I/O Bus B) |
| Longer equivalents | 16137-151 (M-Bus A, 4 m) · 16137-152 (M-Bus A, 15 m) |
| Bus-end terminator | 16137-173 (M-Bus “A” termination plug); “B” side uses 16137-176 |
| Connectors | OEM keyed / polarised, factory crimped, mis-mate protected, locking latches |
| Cable construction | Shielded, impedance-matched to the APACS+ bus spec; flame-retardant industrial jacket, moulded strain relief |
| Bus rule | A and B paths independent; equal length not required, but both must be intact and terminated at both ends |
| Lifecycle | Discontinued by Siemens — surplus / refurbished supply only |
| Shipping weight | ~0.5 kg class (cable assembly, in carton) |
Typical Applications
- Short in-cabinet M-Bus runs — the 2.5 m span is the correct choice where a 4 m cable would leave an excess loop to dress and strain-relieve inside a densely packed MODULERAC cabinet
- Redundant bus pair — installed as the “A” channel with a matched 16137-223 “B” cable to give physically separate primary and standby paths between the ACM pair, I/O nests and interface hardware
- IEM / I/O Extension Module drops — short hops from a Modulrac to an adjacent IEM or an engineering-station interface card
- Cabinet refurbishment — re-cabling after chassis replacement or re-arrangement, or where the original cable shows jacket cracking, bent pins or a fatigued crimp
- Legacy life extension in refining, petrochemical, power, pulp & paper and water treatment plants held online pending migration to SIMATIC PCS 7
Related News & Events
- Catalogue decode is the verification tool. The
-22xblock is a complete 2.5 m family (M-Bus A/B and I/O Bus A/B). Two further suffixes sit outside it: 16137-230 / 231 / 232 / 233 are “I/O Bus A/B IN and OUT to IFI” cables — functionally different again. A buyer who searches only “16137-22…” will land on four plausible-looking, mutually incompatible parts. - Fabricated listings dominate the web results. 16137-222 is most often packaged in spam articles that open by declaring it a “Yokogawa” product and then, in the same page, admit it is a Siemens M-Bus cable — with invented connector types (“high-density M-Bus connector”), invented jacket polymers and invented IP ratings. One page even attaches a 32-channel digital-input-module description to a sibling number. None of it comes from a Siemens document; the only reliable descriptions are the terse catalogue strings.
- Length ambiguity worth flagging. Some US surplus listings show a 2 m “M-Bus B” cable under 16137-158, while the catalogue gives the B-side 2.5 m part as 16137-223. Both numbers exist; at least one listing truncates the cross-reference. Measure the installed run rather than assuming, and check the printed sleeve.
- “M-Bus” naming collision: this is the Moore/Siemens Module Bus, not the EN 1434-3 utility meter bus. Generic RS-485 or metering cable will not substitute — the APACS terminator is matched to both characteristic impedance and DC bias, and a wrong cable shows up as reflections the controller reports as a bus fault.
- Latched faults: an APACS MBUS fault is held in the ACM’s diagnostic logic. Re-seating or replacing the A cable restores the physical layer but does not clear the alarm — recovery requires a controlled power-down/power-up of the redundant ACM pair. Plan re-cabling for an outage, then verify both ACMs hold steady green for five minutes and run a loop check before returning loops to auto.
- Lifecycle: APACS+ / QUADLOG is fully discontinued and out of Siemens support; QUADlog technology was also licensed into Yokogawa ProSafe-PLC, which explains the recurring Yokogawa mislabelling in scraped catalogues. Active installations typically carry a Weidmüller adapter-rack migration path that reuses the existing field terminations.