ABB DSAO120A (3BSE018293R1) 8-Channel Analog Output Module, S100 I/O for Advant OCS / AC450

  1. ABB DSAI130A 3BSE018292R1 (8CH Analog Input)
  2. ABB DSDI110A 3BSE018295R1 Digital Input Module
  3. ABB DSDO115A 3BSE018298R1 Digital Output Module
  4. ABB PM511V16 3BSE011181R1 AC450 CPU
  5. ABB RF533 3BSE014227R1 AC450 Subrack
  6. ABB CI630 AF100 Communication Module
  7. ABB SA811 Power Supply
  8. ABB CI851 MasterBus300E Interface

 

Category: SKU: ABB DSAO120A 3BSE018293R1 8-CHANNEL Brand:

Description

ABB DSAO120A (3BSE018293R1) 8-Channel Analog Output Module, S100 I/O for Advant OCS / AC450

 

Product Overview

DSAO120A is an 8-channel isolated analog output AO card belonging to ABB S100 I/O series for legacy Advant OCS and AC450 (Advant Controller 450) DCS. It converts digital control commands from PM511 CPU into analog 4–20mA / 0–10V signals to drive field control elements such as control valves, actuators and variable speed drives. Every channel features galvanic isolation to suppress field noise and cross-talk. It supports fail-safe output configuration for safety protection upon module or bus failure. This card is discontinued by ABB and supplied as spare replacement for existing Advant OCS plants.

DSAI130A 3BSE018292R1

Key Technical Specifications

  • Part Number: DSAO120A, 3BSE018293R1
  • Manufacturer: ABB
  • Series: S100 I/O, Advant OCS / AC450
  • Channels: 8 isolated analog output channels
  • Signal Type: 4–20mA or 0–10V per channel (configurable)
  • Resolution: 12-bit DAC
  • Channel Isolation: Galvanic isolation between each channel and backplane
  • Power Supply: 24VDC supplied from S100 subrack backplane
  • Mounting: Plug-in module for S100 I/O rack
  • Operating Temperature: -20°C ~ +60°C
  • Storage Temperature: -40°C ~ +85°C
  • Humidity: 5%–95% non-condensing
  • Weight: ~0.46 kg
  • Diagnostics: Front panel LED indicators for module status, bus communication and channel fault
  • Fail-safe: Configurable fail-safe value (hold / low / high)
  • Compliance: CE; RoHS exempt legacy industrial board

 

Recommended 8 Similar Series Models (S100 / AC450 Family)

  1. ABB DSAI130A 3BSE018292R1 (8CH Analog Input)
  2. ABB DSDI110A 3BSE018295R1 Digital Input Module
  3. ABB DSDO115A 3BSE018298R1 Digital Output Module
  4. ABB PM511V16 3BSE011181R1 AC450 CPU
  5. ABB RF533 3BSE014227R1 AC450 Subrack
  6. ABB CI630 AF100 Communication Module
  7. ABB SA811 Power Supply
  8. ABB CI851 MasterBus300E Interface

 

Quality Control & Test Standard Operating Procedure (SOP)

  1. Visual Inspection: Inspect PCB, edge gold fingers, front panel LEDs, terminal connectors and label. Confirm part number 3BSE018293R1; check for corrosion, burnt components or bent pins.
  2. Continuity Test: Check backplane edge connector pins, power and signal lines for open or short circuit.
  3. Insulation Resistance Test: Insulation test between 24VDC backplane and each analog output channel.
  4. Power-Up Functional Test: Insert DSAO120A into rack, apply 24VDC power, verify LED boot sequence, no overheating.
  5. DAC Output Calibration Test: Send digital setpoints, measure each channel’s 4–20mA /0–10V output, verify accuracy and linearity.
  6. Channel Isolation Test: Verify no cross interference between different AO channels.
  7. Fail-safe Mode Test: Simulate backplane communication loss, confirm output switches to pre-configured fail-safe state.
  8. Bus Communication Test: Communicate with PM511 CPU, verify setpoint download and diagnostic status upload.
  9. Environmental Burn-in Test: Continuous powered burn-in at rated ambient temperature for early failure screening.
  10. Final Recheck & Documentation: Repeat channel calibration and communication test, generate serial-number traceable test report before anti-static packaging.

 

New Module Installation Guide

  1. Pre-Install Preparation: Execute LOTO lockout-tagout procedure for DCS cabinet. Wear ESD wrist strap. Confirm DSAO120A compatible with PM511V16 and rack.
  2. Rack Slot Inspection: Inspect subrack backplane gold connectors for oxidation or bent pins.
  3. Module Insertion: Insert DSAO120A into I/O slot, push fully seated and fasten front retaining screws.
  4. Field Wiring: Wire each AO channel to field valve/actuator. Use shielded twisted pair cable, follow Advant OCS grounding specification.
  5. Power Restore: Energize cabinet 24VDC control power. Observe front panel LED status, wait for module initialization and bus link-up.
  6. Commissioning & Calibration: Connect Advant Builder engineering workstation, assign channel parameters (4–20mA /0–10V), set fail-safe mode, perform channel calibration.
  7. Loop Simulation Test: Send different setpoints, verify analog output accuracy and valve response. Check channel fault diagnostics.
  8. Post-Installation Documentation: Record serial number, channel configuration and calibration data in plant maintenance log.

 

Application Scenarios & Features

Application Scenarios

  • Legacy ABB Advant OCS / DCS for thermal power boiler and turbine control
  • Petrochemical, pulp & paper process control regulation loops
  • Output control signal to control valves, actuators and VFD drives
  • Spare replacement for failed analog output card in I/O rack

Core Features

  • 8-channel galvanically isolated analog output for continuous process regulation
  • Configurable signal: 4–20mA current or 0–10V voltage output
  • 12-bit high precision DAC for accurate control loop regulation
  • Configurable fail-safe output to protect process during communication or hardware failure
  • Built-in per-channel diagnostic for open circuit and hardware fault detection
  • Plug-in hot-swappable I/O module for rack
  • Native integration within ABB Advant OCS / DCS ecosystem

 

FAQ

Q1: What is the difference between and DSAI130A?

A1: is Analog Output (AO) card sending signal to field devices. DSAI130A is Analog Input (AI) card reading field sensor signals.

Q2: Can be hot swapped?

A2: Mechanically hot plug supported. If the channel is controlling live regulating loop, removing the card will lose valve control; replace only in maintenance window.

Q3: What is fail-safe function?

A3: When module loses communication with CPU, AO output can be pre-set to hold value, minimum or maximum value to avoid process hazard.

Q4: Is SIL certified?

A4: SIL certification applies to the complete safety function, not standalone I/O module.

Q5: What common failures of ?

A5: DAC chip drift, channel output open/short, gold finger oxidation, output driver circuit damage.

Q6: Is still produced by ABB?

A6: Discontinued. Only new surplus or refurbished spare parts available for existing Advant OCS plant maintenance.

Q7: What controller works with ?

A7: Mainly PM511 series CPU via I/O rack.

Q8: Can each channel select mA or V separately?

A8: Yes, each channel can be individually configured for current or voltage signal via engineering software.