Description
Woodward SPM-D11 8440-1713/D Synchronizer & Load Share Controller
Product Title
Woodward 8440-1713/D | SPM-D11 Digital Synchronizing & Load Sharing Controller, Panel Mount Generator Paralleling Unit
Product Description
8440-1713/D belongs to the classic SPM-D11 family, a microprocessor-based synchronizer and load share controller for synchronous generator paralleling. It automatically matches voltage, frequency and phase angle between generator and busbar before breaker closure. Supports isochronous / droop kW & kVAR load sharing for multiple gensets. It outputs analog trim signals to engine governor and generator AVR for speed and voltage adjustment. It integrates out-of-sync blocking protection, voltage/frequency monitoring, breaker control logic. Local operation via front LCD & keypad; full parameter configuration and backup through Woodward SPM-D11 PC software. The suffix /D indicates hardware/ firmware variant, defined CT/PT input rating and option package. Widely used for marine power station, island microgrid, CHP and multi-generator industrial prime/backup power.
Technical Specifications
| Item | Parameter |
|---|---|
| Brand | Woodward (伍德沃德) |
| Model | SPM-D11, P/N:8440-1713/D |
| Mounting | Panel mount, 144×72 mm DIN 43700 cutout |
| Power Supply | 9.5 ~ 32 VDC (nominal 12/24 VDC) |
| Max Power Consumption | 12 W |
| PT Measuring Input | 100 VAC / 400 VAC (model variant defined) |
| CT Measuring Input | 1 A or 5 A (depends on suffix /D configuration) |
| Frequency Range | 40 ~70 Hz (50/60 Hz systems) |
| Accuracy | Class 1 |
| Control Output | Analog ±0~10V trim for governor speed & AVR voltage |
| Relay Outputs | Potential-free relay contacts for breaker, sync permissive, alarms |
| Communication | RS485 Modbus RTU |
| Operating Temperature | -20°C ~ +70°C |
| Storage Temperature | -40°C ~ +85°C |
| Humidity | 5~95% non-condensing |
| Front Protection | IP42, IP54 with gasket fitted |
| Certifications | CE, UL/cUL |
| Weight | Approx. 0.8 kg |
| Diagnostics | Loss of voltage, phase imbalance, CT/PT wiring fault, out-of-sync interlock |
Compatibility & Installation Pitfalls
Compatibility
- Equipment:Diesel / gas synchronous generators
- Partner controls:Woodward 505 / 505E turbine governor, generator AVR, easYgen genset controllers
- Sensors:Voltage transformer PT, Current transformer CT
- Host:PLC / SCADA via Modbus RTU
- Not compatible:SPM-D10 old generation; cannot fully replace all-in-one easYgen-3500 (8440-1936)
Critical Installation Pitfalls
- CT safety rule: Short CT secondary terminals before disconnecting wiring. Open CT secondary will generate lethal high voltage.
- Verify suffix /D configuration: 8440-1713/D CT/PT rating must match site transformers; mismatched CT/PT causes wrong power reading and load share imbalance.
- Analog load-share bus: Load sharing interconnection cable must use shielded twisted pair, separate routing away from high power cables to reduce noise.
- Parameter backup: Save full configuration file before replacement. Without backup, synchronizing window, droop, load share and protection parameters must be re-programmed.
- DC control power: Use battery supply with surge suppression. Do not share circuit with engine starter, voltage dip will reset controller.
- Panel gasket: Install sealing gasket to achieve IP54 front protection, prevent cabinet condensation and dust ingress.
- Not hot-swappable: De-energize DC control power and implement LOTO before removal. Live removal loses synchronizing & load share protection, risk of generator damage.
Standard Operating Procedure (SOP)
- Pre-Install Inspection & LOTO Lock out generator high voltage and DC control power. Inspect LCD, keypad and rear terminal block, confirm part number 8440-1713/D. Prepare SPM-D11 PC configuration software.
- Panel Mounting Insert into 144×72 panel cutout, fit sealing gasket and secure mounting clips.
- PT/CT, Control & Communication Wiring Wire PT voltage, CT current inputs, governor/AVR analog trim outputs, breaker relay outputs and RS485 Modbus. Use shielded twisted pair. Complete insulation and continuity test.
- Controller Configuration Set genset rated parameters, synchronizing window, droop / isochronous mode, kW/kVAR load share parameters, alarm and permissive logic. Save configuration file.
- Power-Up & Commissioning Apply DC control power. Verify voltage, current and frequency readings. Perform dead bus test, no-load synchronizing test, multi-unit load sharing test. Validate out-of-sync blocking protection.
- Runtime Operation & Diagnostics Monitor sync status, load sharing and alarms via front panel or SCADA. Regularly backup configuration file.
- Replacement Procedure Execute LOTO. Short CT secondary first, then disconnect all wiring. Remove old . Install spare 8440-1713/D, rewire, restore saved parameters and run full commissioning & protection verification.
Application Scenarios
- Multi-generator paralleling power plants
- Marine vessel power management and shore power synchronization
- Island microgrid and peak shaving systems
- Oil & gas prime power, CHP combined heat & power
- Industrial multi-set backup power station
- Retrofit and spare replacement for legacy generator parallel control
Supporting Components
- 144×72 panel mounting kit and sealing gasket
- Current transformer CT & voltage transformer PT
- 12/24VDC surge protected battery power supply
- PC configuration software
- Shielded twisted pair for analog load-share and Modbus wiring
- Woodward governor (505/505E) and generator AVR
- Circuit breakers and terminal blocks
- PLC/SCADA host for remote monitoring
- Generator breaker interlock logic
- Load-share termination resistors
Related Model Recommendations (10 Models)
- 8440-1706 SPM-D11
- 8440-1936 easYgen-3500 genset controller
- Woodward 505 / 505E turbine governor
- 8440-2299 DSLC-2XT load share controller
- 8440-2297 DTSC-200A synchronizer
- CLS216 Watlow 16-loop temperature controller
- CLS204 Watlow 4-loop temperature controller
- WAGO 758-873 PFC200 PLC
- MCS2000-ECA Warner tension controller
- VM600 MPC4 Vibro-Meter vibration protection card