Description
Woodward 1751-6058 Dual-Coil Fuel Shutoff Solenoid, Engine Emergency Stop Actuator
Product Description
The 1751-6058 is a Woodward dual-coil pull-and-hold fuel shutdown solenoid, designed for diesel and gas engine emergency fuel cutoff. It adopts a two-stage coil architecture: a high-current pull coil for rapid plunger actuation, and a low-power hold coil to maintain shutdown status after triggering. Widely deployed in gensets, marine propulsion, heavy-duty industrial engines and turbine auxiliary safety loops. It provides reliable positive fuel shutoff upon trip signals, compliant with engine safety protection requirements.

1751-6058
Technical Parameters
| Item | Specification |
|---|---|
| Manufacturer | Woodward |
| Model | 1751-6058 |
| Coil Type | Dual coil (Pull + Hold) |
| Rated Voltage | 24 VDC |
| Pull Coil Peak Current | ~10 A (short-duration) |
| Hold Coil Operating Current | ~0.8–1.2 A |
| Actuation Time | ≤150 ms |
| Housing Material | Die-cast aluminum, sealed construction |
| Insulation Class | Class H |
| Operating Ambient Temp | -40 ℃ ~ +85 ℃ |
| Shock & Vibration | Compliant with SAE J1455 |
| Ingress Rating | IP65 |
| Termination | 3-wire: Pull, Hold, Common |
| Mounting | Direct flange mount to engine fuel pump |
| Weight | Approx. 0.75 kg |
Recommended Alternative & Related Models (8 pcs)
- 1751-6058B: Revised 24V version with enhanced EMI suppression
- 1751-12E2U1B1: 12V dual-coil shutoff solenoid
- 1751-24E2U1B1: Standard 24V base model
- 1751ES-24E7U1B1S5: ES series improved thermal variant
- SA-4984-24: Cross-referenced equivalent shutoff actuator
- 1753-12E2U1BS1: 12V marine ignition-protected model
- 3864274: Cummins drop-in replacement solenoid
- 1751-6060: High-temperature 24V variant for exhaust-proximity installation
Compatibility & Installation Traps
Compatibility
- Matches most heavy-duty diesel/gas genset engines with mechanical fuel injection pumps.
- Works with Woodward 505 / 505E turbine controllers, engine safety trip relay systems and PLC discrete trip outputs.
- Signal source: dry contact trip relay; not compatible with continuous high-current outputs without intermediate relay isolation.
Critical Installation Traps
- Voltage Mismatch Risk: Never apply 24V to 12V coil versions; pull coil will burn out within seconds. No simple resistor conversion is available.
- Pull Coil Duty Limit: Pull coil is only rated for transient pulse. Continuous energization of pull coil causes permanent thermal damage. Control circuit must switch automatically to hold coil after actuation.
- Mechanical Binding: Plunger must fully bottom after pull-in. Partial stroke leads to coil overheating and incomplete fuel shutoff.
- Wiring Resistance: Excessively long thin wires create large voltage drop; insufficient pull force fails to trigger shutdown. Use ≥14AWG copper for power leads.
- ESD & Grounding: Static damage to internal switching components during service. Always use anti-static bags and wrist straps. Separate solenoid power ground from instrument signal ground to avoid noise interference.
- Ignition Protection Requirement: Marine hazardous zone applications must select models marked “ignition protected”; standard 1751-6058 is not certified for Class I Div 1 locations.
- Reverse Polarity: Reverse DC polarity may damage internal diode protection circuits. Verify polarity with multimeter before power-up.
Standard Operating Procedure (SOP)
- Pre-installation inspection: Check housing for cracks, seal degradation, and coil resistance against datasheet tolerance (±10%).
- Mechanical mounting: Fasten solenoid flange squarely to fuel pump, confirm plunger linkage has no binding or excessive free play.
- Wiring: Terminate pull, hold and common leads strictly per Woodward wiring diagram. Install an interposing relay for controller output isolation.
- Continuity test: Power the circuit for a short test pulse; confirm audible plunger pull-in and latching. Measure hold current to validate coil switching.
- Functional trip test: Trigger the engine safety trip circuit, verify fuel supply cuts off reliably. Reset and confirm engine can restart after reset command.
- Periodic maintenance: Annual resistance check, visual seal inspection, and full functional trip test after every emergency shutdown event.
- Decommissioning: Isolate battery power first; store spare units in sealed anti-static packaging under dry indoor conditions.

1751-6058
Application Scenarios
- Diesel/gas generator set emergency stop protection
- Marine main and auxiliary engine fuel safety shutoff
- Industrial heavy-duty engine over-speed, low-oil-pressure and high-temperature trip loops
- Steam/gas turbine auxiliary fuel cutoff linked to Woodward 505 control systems
- Off-highway construction machinery engine safety protection
Supporting Components
- Interposing 24VDC trip relay
- Anti-static service kit (wrist strap, shielding bags)
- Crimp terminals and heat-shrink wiring harness
- Plunger linkage adapter kit
- Overcurrent circuit breaker (fast-acting for pull-coil protection)
- Woodward 505View configuration software for trip logic setup
- Replacement flange gasket and sealing O-ring set