Description
Schneider Electric 140DRA84000 — Modicon Quantum Relay Output Module, 16 Outputs, 20–250 V AC / 5–150 V DC

140DRA84000
Main Technical Specifications
| Parameter | Value |
|---|---|
| Brand / Manufacturer | Schneider Electric |
| Range | Modicon Quantum automation platform |
| Product type | Relay discrete output module |
| Number of outputs | 16, each with 1 NO contact (Form A) |
| Output voltage range | 20…250 V AC; 5…30 V DC; 30…150 V DC (derated) |
| Min. load | ≥50 mA |
| Max load current | 2 A per point resistive @ 250 V AC / 30 V DC (60 °C); 1 A inductive (1/8 hp, cos φ = 0.4); 1 A tungsten lamp; 300 mA resistive @ 30–50 V DC (100 mA at L/R = 10 ms) |
| Surge current | 10 A for 10 ms (capacitive) |
| Switching capacity | 500 VA resistive |
| Response time | ≤10 ms (0→1); ≤20 ms (1→0) |
| Life | Mechanical ~10⁷ operations; electrical 2×10⁵ (2 A, 250 V AC resistive) / 10⁵ (2 A, 30 V DC) |
| Isolation | 1780 Vrms AC between channels (1 min); 1780 Vrms AC / 2500 V DC channel-to-bus (1 min) |
| Bus current requirement | ~1100 mA |
| Power dissipation | 5.5 W + 0.5 W × (points ON) |
| External power | Not required |
| Addressing | 1 output word |
| Local signalling | 16 green channel LEDs + 1 green RUN/bus LED; fuse cut-out area on front panel |
| Operating temperature | 0…60 °C |
| Weight | 0.41 kg |
| Certifications | UL 508, CSA, CE, C-Tick, FM Class 1 Division 2 |
| Variant | 140DRA84000C — conformally coated version for corrosive/humid environments |
Key Advantages
- Universal voltage compatibility — one module switches 220 V AC contactors, 24 V DC solenoids, and 48–125 V DC circuits alike, covering most mixed plant control schemes without intermediate relays
- Robust relay isolation — dual metal contacts with galvanic isolation protect the backplane from field surges
- No external supply needed — powered entirely from the rack
- Easy diagnostics — per-channel LEDs and front-access fuse area speed commissioning and troubleshooting
Typical Applications
- Process industries (oil & gas, chemical, refining): solenoid valves, pneumatic valve control, interlock and alarm circuits
- Power & energy: breaker auxiliaries, annunciation, control relay interfacing
- Building & infrastructure: lighting circuits, ventilation fans, access control directly at 220 V AC
- Heavy industry (metallurgy, paper): contactor coils, indicator lamps, buzzers
- Legacy Quantum maintenance: a classic spare for brownfield Quantum installations
Usage Notes
- Relay outputs are not suitable for high-speed pulse, positioning, or counting tasks — response is 10–20 ms vs. transistor modules’ microsecond range.
- For inductive loads (valve coils, contactors), apply RC snubbers or interpose relays to extend contact life; respect derating on 30–150 V DC circuits.
- Market status: the module is widely reported as phased out of production; current supply is mainly new-surplus and refurbished stock. Schneider recommends checking availability of the conformal-coated 140DRA84000C variant and the M580 migration path for long-term projects.