ABB CI630 (3BSE011000R1) AF100 Communication Interface Module for Advant Controller 450 (AC450) / Advant OCS

  1. ABB CI630K01 3BSE011001R1 (Single kit)
  2. ABB CI630K02 3BSE011002R1 (Redundant kit)
  3. ABB PM511V16 3BSE011181R1 ( CPU)
  4. ABB RF533 3BSE014227R1 (12SU subrack)
  5. ABB CI851 MasterBus300E Interface
  6. ABB SA811 Power Supply
  7. ABB AI810 Analog Input Module
  8. ABB AO810 Analog Output Module

 

Category: SKU: ABB CI630 3BSE011000R1 AF100 Brand:

Description

ABB CI630 (3BSE011000R1) AF100 Communication Interface Module for Advant Controller 450 (AC450) / Advant OCS

 

Product Overview

The ABB CI630 is an AF100 communication interface module for legacy ABB Advant OCS / AC450 DCS platform. It is equipped with an integrated modem and coaxial connectors, responsible for connecting the AC450 controller to the AF100 plant-wide field communication bus. AF100 is ABB’s old plant loop bus, used to exchange process values, alarms and control commands between AC450 controllers, remote I/O stations and operator stations. There are two kit versions: CI630K01 for single AF100 connection and CI630K02 for redundant AF100 bus. This module is fully discontinued by ABB, only supplied as spare replacement for existing Advant OCS plants.

ABB 3BSE011000R1 CI630

Key Technical Specifications

  • Part Number: CI630, 3BSE011000R1
  • Manufacturer: ABB
  • Product Type: Communication Interface Module
  • Platform: Advant Controller 450 (AC450), Advant OCS
  • Bus Interface: plant bus, integrated modem, coaxial BNC connectors
  • Mounting: Plug-in module for AC450 RF533 / RF520 subrack
  • Power Supply: 24VDC from subrack backplane
  • Operating Temperature: -20°C ~ +60°C
  • Storage Temperature: -40°C ~ +85°C
  • Relative Humidity: 5%–95% non-condensing
  • Dimensions (W×H×D): 40 × 252 × 273 mm
  • Weight: ~1.42 kg
  • Diagnostics: Front panel LED indicators for bus status, link, fault alarm
  • Compliance: CE; RoHS exempt for legacy industrial control equipment
  • Redundancy Option: CI630K02 kit supports redundant bus connection

 

Recommended 8 Similar Series Models ( / Advant OCS Family)

  1. ABB CI630K01 3BSE011001R1 (Single kit)
  2. ABB CI630K02 3BSE011002R1 (Redundant kit)
  3. ABB PM511V16 3BSE011181R1 ( CPU)
  4. ABB RF533 3BSE014227R1 (12SU subrack)
  5. ABB CI851 MasterBus300E Interface
  6. ABB SA811 Power Supply
  7. ABB AI810 Analog Input Module
  8. ABB AO810 Analog Output Module

 

Quality Control & Test Standard Operating Procedure (SOP)

  1. Visual Inspection: Inspect PCB, front panel, BNC coaxial connectors, edge gold fingers and labels. Confirm part number 3BSE011000R1; check for corrosion, burnt components or bent pins.
  2. Continuity Test: Check backplane edge connector pins, power and signal lines for open/short circuit.
  3. Insulation Resistance Test: Insulation test between 24VDC power and coaxial signal circuit.
  4. Power-Up Functional Test: Insert module into subrack, apply 24VDC power, verify LED boot sequence, no overheating.
  5. Modem Communication Test: Connect BNC coaxial cable to bus simulator. Verify modem handshake, data transmit/receive.
  6. Fault Diagnostic Test: Simulate bus break or short, confirm fault LED trigger and fault signal feedback to PM511 CPU.
  7. Redundancy Test (CI630K02 only): Test automatic switchover between primary and standby bus.
  8. Environmental Burn-in Test: Continuous powered burn-in under rated temperature for early failure screening.
  9. Final Recheck & Documentation: Repeat communication and diagnostic test, generate serial-number traceable test report before anti-static packaging.

 

New Module Installation Guide

  1. Pre-Install Preparation: Execute LOTO lockout-tagout procedure for DCS cabinet. Wear ESD wrist strap. Confirm CI630 matches bus requirement and compatible with PM511V16 CPU.
  2. Rack Slot Inspection: Inspect RF533/RF520 subrack backplane gold connectors for oxidation or bent pins.
  3. Module Insertion: Insert CI630 module into subrack slot, push fully seated and fasten front retaining screws.
  4. Coaxial Wiring: Connect BNC coaxial cable to CI630 port. Terminate bus terminator at the end of bus loop, follow Advant OCS shielding and grounding rules.
  5. Power Restore: Energize cabinet 24VDC control power. Observe front panel LED status, wait for module initialization and bus link-up.
  6. Commissioning & Bus Test: Connect Advant Builder engineering workstation, run system self-test, verify bus communication between controller, remote I/O and operator stations.
  7. Data Exchange Simulation: Verify process variable, alarm and command transmission over bus.
  8. Post-Installation Documentation: Record serial number, bus parameters and commissioning results in plant maintenance log.

ABB 3BSE011000R1 CI630

Application Scenarios & Features

Application Scenarios

  • Legacy ABB Advant OCS / DCS in thermal power plants, boiler & turbine control
  • Petrochemical, pulp & paper process control plant bus networking
  • Spare replacement for failed communication interface
  • Interconnection between controllers, remote I/O and Advant operator stations

Core Features

  • Dedicated plant bus communication interface with built-in modem
  • BNC coaxial connector for loop bus, long-distance plant field communication
  • Works with PM511V16 CPU in RF533 / RF520 subrack
  • Optional redundant bus configuration via CI630K02 kit for high availability
  • Onboard LED diagnostics for fast bus fault troubleshooting
  • Plug-in hot-swappable design for rack
  • Native integration within ABB Advant OCS / DCS ecosystem

 

FAQ

Q1: What is bus?

A1: is ABB legacy plant communication bus for Advant OCS, using coaxial cable. It links controllers, remote I/O and operator stations across plant areas.

Q2: What is the difference between CI630K01 and CI630K02?

A2: CI630K01 is single bus kit. is redundant dual bus kit for high availability, supporting automatic bus switchover.

Q3: Can be hot swapped in rack?

A3: Mechanically hot plug supported. Removing active will disconnect bus communication; replace during plant maintenance window.

Q4: Is SIL certified?

A4: SIL certification applies to complete safety function, not standalone communication module.

Q5: What common failures for ?

A5: BNC connector aging, modem circuit failure, gold edge contact oxidation, bus signal attenuation.

Q6: Is still produced by ABB?

A6: Discontinued. Only new surplus or refurbished spare parts available for existing Advant OCS plant maintenance.

Q7: What is the difference between and CI851?

A7: = plant bus interface. CI851 = MasterBus300E backplane bus interface inside rack.

Q8: What cable does use?

A8: 75Ω coaxial cable with BNC connectors, bus loop requires proper terminal resistor.