Description
ABB 5SHX1960L0004 IGCT Thyristor | Medium Voltage Power Semiconductor Spare
Product Overview
The ABB 5SHX1960L0004 is an asymmetric Integrated Gate-Commutated Thyristor (IGCT, often referred to as high-power thyristor) in press-pack construction, widely adopted as the core power switching component for ABB ACS1000, ACS600 medium voltage drives, SVC Light and STATCOM power conversion systems. It combines the high surge current capacity of conventional thyristors with fast, reliable gate-controlled turn-off capability.We maintain ready stock for this part, together with the full 5SHY series IGCT portfolio, supporting urgent replacement, power stack overhaul and plant spare inventory setup for power, mining, oil & gas and renewable energy converters. Its press-pack package features double-sided cooling and a short-circuit-safe failure mode, delivering outstanding stability for series-connected valve stacks.

5SHX1960L0004
Key Technical Specifications
| Item | Parameter |
|---|---|
| Part Number | 5SHX1960L0004 |
| Device Type | Asymmetric IGCT (Gate Commutated Thyristor) |
| Rated Blocking Voltage | 4500 V |
| Nominal Turn-off Current | 1960 A |
| Package Style | Press-pack, double-sided cooling |
| Matched System | ACS1000, ACS600 MV Drives, SVC, STATCOM |
| Mounting Method | Clamped between copper heat sinks with defined compression force |
| Operating Junction Temp | -40°C ~ +125°C |
| Storage Temperature | -40°C ~ +130°C |
| Customs HS Code | 85413000 |
| Origin | Europe |
| Compatibility | Can be series-connected with proper snubber & voltage balancing circuit |
Quality Control Procedure
- Visual & Package Inspection: Verify press-pack body integrity, sealing surface, marking laser code and ESD packaging; check for scratches, cracks or oxidation on contact planes.
- Static Parameter Test: Test reverse/forward blocking, leakage current and gate loop continuity on semiconductor tester.
- Dynamic Switching Test: Validate turn-on, snubberless turn-off performance and gate trigger characteristic under rated test bench condition.
- Thermal Cycle Screening: Controlled thermal cycling to expose hidden die bonding defects.
- Pressure Contact Simulation: Check contact flatness to avoid hotspots after stack assembly.
- Document & Labeling: Attach individual test report, mark serial number, pack with anti-static and shockproof protection before shipment.
Related 5SHY Series IGCT Models (15pcs, all in stock)
- 5SHY35L4510
- 5SHY35L4511
- 5SHY35L4512
- 5SHY35L4520
- 5SHY35L4521
- 5SHY35L4522
- 5SHY3545L0005
- 5SHY3545L0006
- 5SHY3545L0009
- 5SHY3545L0010
- 5SHY3545L0014
- 5SHY3545L0016
- 5SHY3545L0020
- 5SHY42L6500
- 5SHY55L4500
Frequently Asked Questions
Q1: What is the difference between IGCT and ordinary SCR thyristor?A: IGCT supports forced gate turn-off while standard SCR can only be turned off by current commutation. This makes IGCT suitable for high-power voltage-source converters like MV drives and static var compensators.
Q2: Can 5SHX1960L0004 directly replace 5SHY series IGCT?A: Not interchangeable directly. Confirm voltage class, turn-off current rating, mechanical thickness and gate unit compatibility before substitution.
Q3: Is press-pack IGCT repairable once damaged?A: No. Once the internal wafer fails, the whole device must be replaced. The contact surfaces must be protected from scratch and contamination.
Q4: What are common failure signs of faulty IGCT?A: Continuous high leakage current, converter valve short-circuit alarm, uneven temperature rise in the power stack, drive fault trip under load.
Q5: What is your lead time and warranty?A: Most 5SHX / 5SHY IGCT items are available from local stock for prompt shipment. Standard 12-month functional warranty, excluding damage caused by incorrect clamping force, overvoltage and improper cooling.
Installation & Configuration Guide
Critical Warning: Press-pack IGCT installation requires specified clamping force. Improper pressure causes thermal runaway or early device failure.
- Prep Work: Isolate all high voltage, implement lockout-tagout. Prepare torque-controlled clamping tools, contact grease, cleaning wipes and ESD protection.
- Surface Cleaning: Thoroughly wipe both metal contact planes of IGCT and heat sink to remove dust, burr and old thermal compound.
- Stack Assembly: Place the IGCT aligned concentrically between heat sink plates. Follow manufacturer specification for clamping force. Do not over-torque.
- Gate Unit Wiring: Connect gate fiber / control cable carefully; avoid fiber bending below minimum radius.
- Pre-power Check: Measure blocking leakage of each IGCT in stack; verify fiber communication between gate drive and control system.
- Low-Voltage Commissioning: Run dry test without high DC-link voltage to check trigger and turn-off sequence.
- Energize & Thermal Monitoring: Apply operating voltage gradually; use thermal monitoring to confirm even temperature distribution on each device.
- Post-install Record: Record serial number, clamping force, thermal reading and stack position for maintenance tracking.