140SDI95300S — Schneider Electric Modicon Quantum Safety DC Discrete Input Module (16 Inputs, 24 V DC)

Related Product Recommendations

Model Description
BMXSDI1602 Modicon X80 safety discrete input module, 16 inputs, 24 V DC — official replacement
140 CPU 651 50S / 140 CPU 658 60S Quantum safety CPUs required to configure this module (Unity Pro Safety)
140SDO95300D Quantum safety DC discrete output module — the matching safety output side
140CRA / 140CRP series Quantum remote I/O adaptors for distributed safety I/O architectures
140CPS12420 Quantum rack power supply for safety racks
Modicon M580 Safety (BMEH58…) + X80 Recommended migration platform for SIL-rated applications
Category: Brand:

Description

140SDI95300S — Schneider Electric Modicon Quantum Safety DC Discrete Input Module (16 Inputs, 24 V DC)

140SDI95300S

Brand & Model Title

Schneider Electric 140SDI95300S — Modicon Quantum Safety DC Discrete Input Module, 16 Channels, 24 V DC, TÜV Rheinland SIL2-Certified

The 140SDI95300S is the safety-rated digital input module of the Modicon Quantum safety platform. Purpose-built for safety instrumented systems (SIS), it acquires signals from safety field devices — emergency stop buttons, guard-door switches, light curtains, safety limit switches — while continuously diagnosing wiring integrity and its own internal channels. The “S” suffix denotes the safety-dedicated version: it can only be configured with a Quantum safety CPU (140 CPU 65x50S / Unity Pro Safety), not with standard Quantum processors.

 

Main Technical Specifications

Parameter Value
Product type Safety DC discrete input module
Platform Modicon Quantum automation platform (safety architecture)
Inputs 16 discrete inputs, 1 group, positive logic (sink)
Rated input voltage 24 V DC (sensor power supply range 19.2…30 V)
State 1 guaranteed 11…30 V DC; current ≥ 3 mA
State 0 guaranteed −3…5 V DC; current ≤ 1.5 mA
Input impedance / absolute max 3675 Ω / 30 V
Response time ≤ 25 ms (0→1 and 1→0)
Addressing requirement 7 input words (channel status, line-fault, channel validity, power status, CRC checks, module health)
Diagnostics Internal channel fault diagnosis, system failure, broken-wire detection
Protection Internal rectifier; external fuse 1 A fast-blow; 15 kΩ pull-up required for dry-contact broken-wire monitoring
Power Power dissipation 2.75 W + 0.25 W per active point; bus current 550 mA @ 5 V DC (backplane)
Isolation Group-to-bus 1500 Vrms for 1 minute
Local signalling 1 green LED (bus active), 1 red LED (external fault), 16 green LEDs (input status), 16 red LEDs (system failure / channel fault)
Marking CE; RoHS compliant (EU & China)
Certifications CSA, UL, TÜV Rheinland (SIL2, IEC 61508)​, CSA HazLoc
Lifecycle Discontinued 26 February 2022; end of standard service 31 December 2029

 

Typical Applications

  • Emergency shutdown systems (ESD)​ — acquisition of E-stop and trip signals with broken-wire monitoring to guarantee the safety path stays live
  • Safety instrumented systems (SIS)​ — SIL2 safety functions under IEC 61508 in the Quantum safety architecture (configured with Unity Pro Safety and a Quantum safety CPU)
  • Machine and process protection — guard doors, light curtains, safety limit switches in chemical, petrochemical, power generation and metallurgy plants
  • Turbine and compressor protection — high-integrity input monitoring in continuous-process installations
  • Spare-part replacement for in-service Quantum safety systems through the 2029 support window

 

Related News & Events

  • Official lifecycle status (datasheet dated November 2026):​ discontinued — stop of production 26 February 2022, with end of standard service on 31 December 2029; repair and spare-parts support remains available for roughly three more years.
  • Official replacement announced:​ Schneider Electric directs users to the Modicon X80 series safety discrete input module BMXSDI1602 (16 inputs, 24 V DC) under the Modicon M580/EcoStruxure migration path.
  • Safety certification:​ the module carries TÜV Rheinland SIL2 certification per the official datasheet; some third-party listings claim higher levels (SIL3 / PL e) — the authoritative rating is SIL2, and application-level safety integrity must be verified per the final system design.
  • Engineering notes in circulation:​ the module occupies 7 input words with a rich diagnostic map (health word, line-fault word, CRC checks), letting the program distinguish signal-off from broken wire, internal fault, or lost external supply; dry-contact applications require a 15 kΩ parallel resistor or the channel will continuously flag a line fault.
  • Aftermarket:​ as Quantum safety fleets age, new-surplus and tested units are actively traded by industrial spare-parts distributors with 12-month warranties; buyers must confirm compatibility with a Quantum safety CPU before purchase.