Description
Schneider Electric 140HLI34000 — Modicon Quantum High-Speed Latch / Interrupt Input Module, 16 Channels, 24 V DC

140HLI34000
Main Technical Specifications
| Parameter | Value |
|---|---|
| Brand / Manufacturer | Schneider Electric |
| Range | Modicon Quantum automation platform |
| Product type | High-speed latch / interrupt discrete input module |
| Input channels | 16 independently configurable, optically isolated 24 V DC inputs |
| Device compatibility | Sink (2-/3-wire) or source field devices |
| Input voltage range | 10–30 V DC (max withstand 30 V DC) |
| Logic thresholds | ON: 15–30 V DC; OFF: −3…+5 V DC |
| Input current | ON: 2.0–8.0 mA; OFF: ≤0.5 mA |
| Response time | ~30 µs (ON→OFF) / ~130 µs (OFF→ON) — microsecond-class, 10×+ faster than standard input modules |
| Pulse capture capability | Very narrow pulses; event latch independent of the PLC scan cycle |
| Operating modes | ① High-speed input ② Latch input ③ Hardware interrupt ④ Split mode (each channel freely mixes the above) |
| Isolation | 500 V AC between channels (60 s); 1780 V AC channel-to-backplane (60 s) |
| Protection | Built-in 30 V reverse-polarity protection; configurable input filtering for debouncing |
| Bus current | 400 mA (5 V backplane) |
| Power dissipation | 2.0 W + 0.3 W × (points ON) |
| Local signalling | RUN and fault LEDs; 16 green channel-status LEDs |
| Mounting | Standard Quantum backplane (1 slot), local rack; hot-swappable |
| Operating temperature | 0…60 °C; humidity 5–95 % non-condensing |
| Weight | ~0.4 kg |
| Certifications | CE, UL, CSA |
Key Advantages
- Microsecond-class response — captures extremely narrow pulses that a normal DI module would miss entirely
- Scan-independent event latch — events are timestamped and stored on-module, so timing accuracy doesn’t depend on the CPU scan period
- True hardware interrupts — external events asynchronously interrupt the CPU, enabling immediate response for safety and trip conditions
- Per-channel mode flexibility (split mode) — any mix of high-speed, latched, and interrupt inputs on one module
- Robust isolation & diagnostics — channel-to-channel optical isolation, reverse-polarity protection, per-channel LEDs
Typical Applications
- Safety & protection — emergency-stop capture, safety interlocks, breaker trip and protection-relay event recording
- High-speed sensing — fast proximity switches, pulse triggers, transient fault-signal capture
- Process trip diagnostics — first-out event detection in power, oil & gas, and chemical plants
- Test benches & precision machinery — time-stamped sequence-of-events logging
- Transportation infrastructure — rail signalling and traffic event monitoring
Usage & Lifecycle Notes
- Interrupt mode caveats: interrupt-handling code should be kept proportionate (typically <40 % of program logic) to avoid starving the main scan; very high pulse rates (multi-kHz) are better handled by counter modules such as 140EHC10500 / 140EHC20200.
- Local rack configuration only (not for RIO/distributed drops).
- Lifecycle: discontinued (retirement announced ~2022; factory support running to end of 2027). Conformal-coated variant 140HLI34000C exists. Recommended successor/alternative for new designs: BMXDDI1602 on the X80 (Modicon M580) platform, which supports event latching and hardware interrupts.